Airvex fabric ducts are delivered in labelled sections, with connection zips and the suspension parts for your project. Always follow the installation drawing supplied with your order. The steps below describe a typical installation.
Suspension options
- Steel cableOne row or several parallel rows. The most economical option for long, straight runs.
- Aluminium trackMounted flush to the ceiling or suspended. Gives the neatest look and keeps the duct straight.
- Steel pipeOne row or several parallel rows, for heavy-duty sites and wide spans.
Insulated ducts AV-W and AV-RW use cable or steel pipe suspension.
Installation steps
Check the drawings and the delivery
Compare the labels on each section with the installation drawing, check the suspension parts and confirm the connection size at the air handling unit or fan.
Mark the duct route
Mark the centre line of each duct run on the ceiling or roof structure, with the positions of the end fixings and intermediate supports shown on the drawing.
Install the suspension system
Fix the end brackets and tension the steel cable, or mount the aluminium track or steel pipe at the specified height. Keep the suspension straight and level along the whole run.
Hang the fabric duct
Unpack the sections in order, attach them to the cable hooks or slide them into the track, and join the sections with the zips. Follow the arrows for the air direction and the position of the outlets.
Connect to the air handling unit
Fit the inlet section to the sheet-metal collar with the clamping strap. Keep a straight sheet-metal section of at least three diameters before the fabric duct and avoid tight bends at the inlet.
Start up and check
Start the fan gradually. The duct should inflate smoothly without flapping. Check the static pressure at the inlet, the air pattern of the outlets and the tension of the suspension, then adjust if needed.
Safety and good practice
- Work from suitable lifting platforms and follow site safety rules.
- Keep the fabric clean and dry. Where possible, install after dusty trades have finished.
- Do not use the duct or its suspension to support other equipment.
- For return air, use only AV-RW ducts designed for negative pressure. A standard fabric duct collapses under suction.