Fabric duct airflow & velocity calculator

Enter the airflow and duct size to check the air velocity, choose a suitable duct size and see how the velocity decreases along the duct run. Results are intended for preliminary design.

Input parameters

1 · Duct cross-section

Fabric duct shapes

2 · Airflow

m³/h

3 · Diameter D

mm

4 · Application and noise requirement

Velocity in the duct

Suitable
5.6m/s

Within the recommended velocity range for the selected application.

Velocity 5.6 m/s, Suitable

  • Oversized< 2.0 m/s
  • Suitable2.0 – 7.0 m/s
  • Caution7.0 – 8.0 m/s
  • Too high> 8.0 m/s
Duct cross-section area
0.396 m²
Dynamic pressure
19 Pa
Recommended duct size
D ≥ 640 mmfor velocity ≤ 7.0 m/s
Selected size
D = 710 mmCircular cross-section

Air distribution

Velocity decreases along the duct

A fabric duct discharges air evenly along its whole length, so the velocity is highest at the inlet and falls towards the end of the duct. The first section of the duct is where you should check noise and avoid elbows or changes of direction.

Duct run length

m
Inlet velocity
5.6 m/s
Average discharge per length
200 m³/h per m
Inlet: 5.6 m/s

Duct length from the inlet

  • Oversized
  • Suitable
  • Caution
  • Too high

Air distribution types

Choose outlets by the throw you need

Throw depends on the type of outlet on the duct body. The ranges below are typical values for preliminary selection.

  • Uniform micro-perforation

    0 – 1.5 m

    Very gentle, low-velocity air for zones where people sit for long periods: offices, cleanrooms.

  • Directional micro-perforation

    0 – 3 m

    Gentle airflow at a chosen angle, with a longer throw than uniform micro-perforation.

  • Small nozzles

    3 – 12 m

    Medium throw for production areas, supermarkets and shopping malls.

  • Perforated orifices

    4 – 15 m

    Long throw and strong air supply for factories and warehouses.

  • Large nozzles

    10 – 30 m

    Very long throw for high-ceiling spaces: sports halls, large factories.

Recommended static pressure at the duct inlet

Minimum for lightweight fabric20 Pa
Minimum for medium and heavy fabric50 Pa
Projects that must run quietly25–60 Pa
Standard design≈ 125 Pa
High airflow, long throw required≈ 190 Pa
Systems with many elbows and fittings≈ 250 Pa

Design and installation tips

  • Keep the sheet-metal duct the same size as the fabric duct inlet over a straight length of at least 3 times the diameter.
  • Use elbows with a 1.5D radius upstream of and within the fabric duct system.
  • When the velocity is in the orange zone, avoid elbows or changes of direction close to the duct inlet.
  • For projects that must be quiet, consider a silencer on the sheet-metal section or use an acoustic fabric duct.

Need an exact calculation for your project?

Send us your airflow, layout and ceiling height. An Airvex engineer will select the duct type and air outlets and send you a detailed quotation.

Results on this page are indicative and intended for preliminary design only. Velocity = airflow ÷ duct cross-section area; dynamic pressure is calculated with an air density of 1.2 kg/m³.