Engineering tool
Fabric duct airflow & velocity calculator
Enter the airflow and duct size to check the air velocity, choose a suitable duct size and see how the velocity decreases along the duct run. Results are intended for preliminary design.
Input parameters
1 · Duct cross-section
Fabric duct shapes2 · Airflow
3 · Diameter D
4 · Application and noise requirement
Velocity in the duct
SuitableWithin the recommended velocity range for the selected application.
Velocity 5.6 m/s, Suitable
- Oversized< 2.0 m/s
- Suitable2.0 – 7.0 m/s
- Caution7.0 – 8.0 m/s
- Too high> 8.0 m/s
- Duct cross-section area
- 0.396 m²
- Dynamic pressure
- 19 Pa
- Recommended duct size
- D ≥ 640 mmfor velocity ≤ 7.0 m/s
- Selected size
- D = 710 mmCircular cross-section
Air distribution
Velocity decreases along the duct
A fabric duct discharges air evenly along its whole length, so the velocity is highest at the inlet and falls towards the end of the duct. The first section of the duct is where you should check noise and avoid elbows or changes of direction.
Duct run length
- Inlet velocity
- 5.6 m/s
- Average discharge per length
- 200 m³/h per m
Duct length from the inlet
- Oversized
- Suitable
- Caution
- Too high
Air distribution types
Choose outlets by the throw you need
Throw depends on the type of outlet on the duct body. The ranges below are typical values for preliminary selection.
Uniform micro-perforation
0 – 1.5 mVery gentle, low-velocity air for zones where people sit for long periods: offices, cleanrooms.
Directional micro-perforation
0 – 3 mGentle airflow at a chosen angle, with a longer throw than uniform micro-perforation.
Small nozzles
3 – 12 mMedium throw for production areas, supermarkets and shopping malls.
Perforated orifices
4 – 15 mLong throw and strong air supply for factories and warehouses.
Large nozzles
10 – 30 mVery long throw for high-ceiling spaces: sports halls, large factories.
Recommended static pressure at the duct inlet
| Minimum for lightweight fabric | 20 Pa |
|---|---|
| Minimum for medium and heavy fabric | 50 Pa |
| Projects that must run quietly | 25–60 Pa |
| Standard design | ≈ 125 Pa |
| High airflow, long throw required | ≈ 190 Pa |
| Systems with many elbows and fittings | ≈ 250 Pa |
Design and installation tips
- Keep the sheet-metal duct the same size as the fabric duct inlet over a straight length of at least 3 times the diameter.
- Use elbows with a 1.5D radius upstream of and within the fabric duct system.
- When the velocity is in the orange zone, avoid elbows or changes of direction close to the duct inlet.
- For projects that must be quiet, consider a silencer on the sheet-metal section or use an acoustic fabric duct.
Need an exact calculation for your project?
Send us your airflow, layout and ceiling height. An Airvex engineer will select the duct type and air outlets and send you a detailed quotation.
Results on this page are indicative and intended for preliminary design only. Velocity = airflow ÷ duct cross-section area; dynamic pressure is calculated with an air density of 1.2 kg/m³.